Analysis and Calculation of Inter-turn Short Circuit in Dry-type Air-core Reactor
干式空心电抗器匝间短路的分析与计算
Guilin Wuhan Electric Equipment Manufacture Co., Ltd, Guilin 541004, China
(2026)
Received:08 June 2026,
Revised:2026-07-07,
Accepted:15 July 2026,
DOI:
稿件说明:
移动端阅览
LUO Bing. Analysis and Calculation of Inter-turn Short Circuit in Dry-type Air-core Reactor[J/OL]. Power Capacitor & Reactive Power Compensation, 2026.
DOI:
LUO Bing. Analysis and Calculation of Inter-turn Short Circuit in Dry-type Air-core Reactor[J/OL]. Power Capacitor & Reactive Power Compensation, 2026.DOI:
Analysis and Calculation of Inter-turn Short Circuit in Dry-type Air-core Reactor
This paper analyzes the causes of inter-turn short circuits in dry-type air-core reactors
which are mainly summarized into five types: local overheating
overvoltage
vibration
insulation weakness or aging
and partial discharge
etc. And for several fault conditions
specific cause analysis and judgment are carried out. To quantitatively analyze the physical quantities that change significantly after inter-turn short circuits
the circuit equations after inter-turn short circuits are listed with current as the variable
and a formula for calculating inductance is given. A program is written to calculate the magnitude of the short-circuit current when inter-turn short circuits occur at different positions of the reactor. The calculation results show that the total loop current almost remains unchanged
while the total loop active current changes significantly; when the short-circuit position is in different branches
the change is the largest in the middle (where the minimum number of turns is located)
slightly smaller in the outermost layer
and the smallest in the innermost layer; when the short-circuit position is in the same branch
the change is the largest in the middle and the smallest at the top. Finally
the correctness of the calculation results was verified through experiments.
WANG Yongyong , WEN Xianglong , LIU Hua , et al . Burn-out of dry hollow parallel reactors [J ] . Heilongjiang Electric Power , 2003 , 25 ( 6 ): 423 - 428 .
YU Qunying JIN Xin , HUANG Tao , et al . Field Test and Analysis of Switching Overvoltage of Dry-type Air-core Shunt Reactor [J ] . Jilin Electric Power , 2021 , 49 ( 5 ): 39 - 42
LEI Xiao , LIAO Wenlong , BAI Huan , et al . Fault Analysis of Dry -Type Air -Core Reactor of DC Filter in HVDC Substation Caused by Overvoltage [J ] . Insulators and Surge Arresters , 2022 ( 4 ): 140 - 145