ZHAO QI-CHENG1, WANG MIN2, DING YI-MIN3. Calculating Research on Common Protection Methods and Rated values of 35 kV Shunt Capacitor Bank in 500 kV Substation. [J]. Power capacitor & reactive power compensation, 2008, 29(6): 5-9.
ZHAO QI-CHENG1, WANG MIN2, DING YI-MIN3. Calculating Research on Common Protection Methods and Rated values of 35 kV Shunt Capacitor Bank in 500 kV Substation. [J]. Power capacitor & reactive power compensation, 2008, 29(6): 5-9.DOI:
Calculating Research on Common Protection Methods and Rated values of 35 kV Shunt Capacitor Bank in 500 kV Substation
According to the capacitor bank protection faults leading to the two explosive accidents of capacitors with internal fuse of 35 kV shunt capacitor bank in 500 kV substations
the computer simulation models of 35 kV shunt capacitor banks in 500 kV substation in Zhejiang Province were conducted.The protection signal values caused by different numbers of internal fuses disconnected and the over-voltage undertaken by the other normal capacitor elements and capacitor units were analyzed through simulation computation
And Related protection values of the relevant capacitor banks were raised.