LV DAN, LI DIAN. Analysis of 220kV Capacitor Voltage Transformer’s Hidden Fault. [J]. Power capacitor & reactive power compensation, 2006, (3): 36-38.DOI:
Analysis of 220kV Capacitor Voltage Transformer’s Hidden Fault
摘要
通过现场测试
发现电容式电压互感器的电容量误差在国家标准之内
但电容量异常增加
且三相线电压明显不平衡
经进一步试验分析
判定电容器内部串联电容已部分击穿
提出了电容式压变运行及测试相应注意事项。
Abstract
Based on the practical tests
It is found that the CVT’s capacitance increases abnormally
and the three phase voltages are obviously imbalanced
although the error of CVT′s capacitance is within the requirement specified by the national standard.Through further examination
it can be concluded that the inner in-series capacitors have been partly broken down.The attentions on CVT′s operation and testing are proposed.
关键词
电容式电压互感器电容量异常
Keywords
capacitor voltage transformer(CVT)capacitanceAbnormality