LIU TAO, YANG MAO HUI. A Problem to be Noticed for On-site Dielectric Loss Measurement of the CVT Voltage Dividing Capacitor. [J]. Power capacitor & reactive power compensation, 2002, (3): 34-35.
LIU TAO, YANG MAO HUI. A Problem to be Noticed for On-site Dielectric Loss Measurement of the CVT Voltage Dividing Capacitor. [J]. Power capacitor & reactive power compensation, 2002, (3): 34-35.DOI:
A Problem to be Noticed for On-site Dielectric Loss Measurement of the CVT Voltage Dividing Capacitor
The error caused by loose contact in the dielectric loss factor (tanδ) measurement is analyzed. It is shown that loose contact will make the measured tanδof the voltage dividing capacitor C 2 in the CVT larger than it really is
The method for eliminating this kind of error is proposed.