GUO QING-WEN, HUANG XUAN, YANG XIAO-LIANG, et al. The Influence of Distributed Capacitance on Initial Unbalance Current of H Type Protection. [J]. Power capacitor & reactive power compensation, 2010, 31(1): 15-18.
GUO QING-WEN, HUANG XUAN, YANG XIAO-LIANG, et al. The Influence of Distributed Capacitance on Initial Unbalance Current of H Type Protection. [J]. Power capacitor & reactive power compensation, 2010, 31(1): 15-18. DOI: 10.14044/j.1674-1757.pcrpc.2010.01.006.
The Influence of Distributed Capacitance on Initial Unbalance Current of H Type Protection
摘要
以华新换流站HP12/24滤波电容器组为例
介绍其塔架结构及接线方式
针对电容器组充电调试时初始不平衡电流偏大的问题
分析、查明并验证原因
发现不同电气连接的分布电容对4个桥臂有不同的影响
通过调整接线
改变分布电容的位置
达到了预期理想要求
为其他HVDC工程提供了经验。
Abstract
This paper
taking HP12/24 filters capacitor banks at Shanghai Huaxin converter station as an example
introduces its structure of tower and way of connection
analyzes
checks and verifies such issue as larger initial unbalance current at charging commissioning of the capacitor bank and finds that the distribution capacitance of different electrical connections has different influence on 4 bridge arms.Adjustment of connection
change of position of distribution capacitance and achievement of expected ideal requirement provide experience for other HVDC projects.
关键词
调试桥差保护分布电容不平衡电流固定电位连线
Keywords
commissioningH-type protectiondistribution capacitanceunbalance currentconnection of fixed potential