LIN YU-JIN. Analysis of On-site Measurement Method of Dielectric Loss for Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2011, 32(4): 53-56.
LIN YU-JIN. Analysis of On-site Measurement Method of Dielectric Loss for Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2011, 32(4): 53-56. DOI: 10.14044/j.1674-1757.pcrpc.2011.04.012.
Analysis of On-site Measurement Method of Dielectric Loss for Capacitor Voltage Transformer
With the increasing growth of scale of electric network in China
operation reliability of capacitor voltage transformer(CVT) is very important for the safe operation of the whole electric system.For assuring safe operation of CVT
the measurement of dielectric loss is one of the most important tests for the insulation condition of CVT.In view of actual situation of test on-site
the various methods on measurement of dielectric loss of CVT are analyzed and then verified by AI-6000(C) tester and the differences among different methods of measuring the dielectric loss tangent of CVT are summarized.Based on test data and theoretical analysis
it is concluded that measurement of dielectric loss of CVT by the Self-excited method on-site is feasible
and also some suggestions about the test voltage for the test are proposed.
关键词
常规法自激法电容式电压互感器(CVT)介损
Keywords
conventional methodself-excited methodcapacitor voltage transformer(CVT)dielectric loss tangent