Analysis and Treatment on Abnormal Secondary Voltage of Capacitor Voltage Transformers
the treatment method in case of abnormal secondary voltage of 500 kV capacitor voltage transformers which just puts into operation for three months is introduced;the abnormal secondary voltage is due to the breakdown of internal grading capacitance in the CVT.Through test of CVT and disassembly inspection
it is proved that the main cause of grading capacitance breakdown is the selection of raw material and manufacturing process.Finally
the suggestions for operation
maintenance and production of 500 kV capacitor voltage transformers have been proposed.