Analysis on Less than Zero of Dielectric Loss Test Result for Capacitor Divider in CVT
which appeared in whole capacitance dielectric loss test of typical 110 kV CVT. The reason for such problem is to test the compensation reactor at both ends of the L protection with MOA have not been removed
thus keeping partial signal current flow directly into earth through MOA branch
circuit and changing phase of the signal current. It is shown by theoretical analysis result that such problem is common in case of dielectric loss test of complete set capacitance for such type of CVT
and test personnel should pay attention. For avoiding negative influence of MOA on complete set capacitance dielectric loss of CVT
it is suggested to remove the MOA during the dielectric loss test.