LI SHAN, YILIZHATI, CHANG NINGNING. Analysis on Charge Fault of 750kV Shunt Reactor. [J]. Power capacitor & reactive power compensation, 2014, 35(3): 83-87.
LI SHAN, YILIZHATI, CHANG NINGNING. Analysis on Charge Fault of 750kV Shunt Reactor. [J]. Power capacitor & reactive power compensation, 2014, 35(3): 83-87. DOI: 10.14044/j.1674-1757.pcrpc.2014.03.018.
Analysis on Charge Fault of 750kV Shunt Reactor
摘要
某超高压变电站在调试过程中进行750 kV并联电抗器充电时
差动保护出口跳闸
通过对故障时的波形、数据、一次设备的安装和试验进行了分析
确定了保护动作原因为电抗器末端套管CT极性接反、7521断路器A相的防跳继电器型号错误。在此基础上
对发现缺陷及时进行处理
保证充电成功
确保后续调试项目顺利进行。通过此次故障分析
要正确测量CT的极性
防止因极性接错导致差动误动作尤其重要;对防跳继电器的安装和验收提出了更严格的要求。
Abstract
The differential protection outlet is tripped in the charging of 750 kV shunt reactor during commissioning of certain EHV substation. Through the analysis of waveform
data
installation and test of primary equipment
the reason for the action is due to reverse connection of casing CT polarity at the end of reactor and type mistake of anti-pumping reply of phase a for 7521 circuit breaker. Moreover
the defects found are treated timely so to assure successful charging and smoothness of subsequence commissioning items.Through analysis of the fault it is important to measure correctly polarity of CT and prevent differential action and mal-operation due to wrong connection of polarity;and more strict requirement to the installation and testing of anti-pumping relay is proposed.