Operation Analysis for POW Device of AC Filter Switch at Xingren Converter Station
Since a large amount of reactive power consumption by the converter at the time of convertion
10 panel filters are installed in Xingren converter station for the purpose of reactive power compensation and harmonic filtering. In order to reduce the inrush current and transients
the special closing angle detection device POW is installed at the circuit breaker of panel filter during the control period of circuit breaker.In this paper
the closing operation principle and the control strategy of the POW are introduced
the fault causes of the POW are analyzed since operation from 2007 at Xingren converter station and the suggestions on operation and maintenance of the POW device are proposed.