Published:2015,
移动端阅览
[1]葛少杰,董万光.一起10kV干式铁心电抗器烧毁事故原因分析[J].电力电容器与无功补偿,2015,36(02):89-92.
GE SHAOJIE, DONG WANGUANG. Burnout Fault Analysis of 10 kV Dry-type Reactor. [J]. Power capacitor & reactive power compensation, 2015, 36(2): 89-92.
[1]葛少杰,董万光.一起10kV干式铁心电抗器烧毁事故原因分析[J].电力电容器与无功补偿,2015,36(02):89-92. DOI: 10.14044/j.1674-1757.pcrpc.2015.02.020.
GE SHAOJIE, DONG WANGUANG. Burnout Fault Analysis of 10 kV Dry-type Reactor. [J]. Power capacitor & reactive power compensation, 2015, 36(2): 89-92. DOI: 10.14044/j.1674-1757.pcrpc.2015.02.020.
结合10 k V干式电抗器的外部结构、运行环境、检查情况、后台保护信息等
对一起干式电抗器烧毁事故进行了分析
发现电容器组频繁的投切使系统产生操作过电压
诱使电抗器绕组末端与铜排连接不良处产生大电流、局部放电
最终导致电抗器烧毁
并有针对性地提出防范措施
确保其稳定运行。
In this paper
one burnout accident of 10 k V dry type reactor is analyzed based on its external structure
operation environment
inspection
background protection information etc. It is found that frequent switching of capacitor bank causes the system to generate operating overvoltage
which inducing high current and partial discharge at the poor contacting location between the end of reactor winding and copper bar and
as result
leading burnout of reactor. The specific preventive measures are proposed so to assure stable operation of the reactor.
干式电抗器烧毁连接不良防范措施
dry-type reactorburnoutpoor contactingpreventive measures