As for the issue of disturbance positioning of capacitor switching in the power grid
in this paper
the basic principle of cross S-transform is described and a new kind of disturbance positioning method of capacitor switching is proposed based on the S-transform. The phase difference of start current of disturbance and voltage signal disturbance component is deduced by the use of cross S-transform. Both transient process of capacitor switching circuit and the detection method of transient disturbance voltage and current phase difference are analyzed in detail. The judgments criteria on the position of capacitor switching are described and
at the same time
positioning process is given. The position of disturbance source can be judged accurately through phase difference polarity with combination of multiple point measurement. Finally
the effectiveness of the proposed method is verified by the simulation experiment.