ZHOU CHUNYANG, LAI JIE, LIU KAI, et al. Influence of Closing Inrush Current of 35 kV Shunt Capacitors Group on CVT Fuse. [J]. Power capacitor & reactive power compensation, 2016, 37(4): 58-61.
ZHOU CHUNYANG, LAI JIE, LIU KAI, et al. Influence of Closing Inrush Current of 35 kV Shunt Capacitors Group on CVT Fuse. [J]. Power capacitor & reactive power compensation, 2016, 37(4): 58-61. DOI: 10.14044/j.1674-1757.pcrpc.2016.04.012.
Influence of Closing Inrush Current of 35 kV Shunt Capacitors Group on CVT Fuse
through the analysis of the fault record data at the fusing moment in 35 k V CVT HV side
the main reason of fuse of HV fuse has been found that it is not due to the ferroresonance overvoltage. CVT simulation model of 35 k V busbar is set up by way of Matlab/Simulation platform and the transient voltage and current of the primary side of CVT at the switching of capacitor bank is simulated and analyzed. It is concluded that the main reason of frequent fuse of fuse is due to the transient high frequency current passing through the primary side of CVT in the switching of capacitor bank
and the current magnitude is related to the phase angle of voltage at the moment of closing operation. Finally
such suggestion as increase of rated current of fuse or elimination of fuse protection is given in accordance with the engineering practice.
关键词
电容式电压互感器(CVT)高压熔断器暂态电压高频电流相位角
Keywords
capacitor voltage transformer(CVT)high-voltage fusestransient voltagehigh frequency currentphase angle