JIN BAIRONG, LI DIAN, CAI ZHONGKAI, et al. Fault Analysis on Switching Overvoltage of 35 kV Shunt Reactor. [J]. Power capacitor & reactive power compensation, 2016, 37(5): 107-112.
JIN BAIRONG, LI DIAN, CAI ZHONGKAI, et al. Fault Analysis on Switching Overvoltage of 35 kV Shunt Reactor. [J]. Power capacitor & reactive power compensation, 2016, 37(5): 107-112. DOI: 10.14044/j.1674-1757.pcrpc.2016.05.022.
Fault Analysis on Switching Overvoltage of 35 kV Shunt Reactor
摘要
针对近年来频发的35 kV并抗开断过电压故障
对多起故障实例进行了汇总调查
对故障现象及规律进行了分析
对故障原因及机理进行了仿真解析
对过电压治理措施进行了研究验证。调查发现35 kV并抗开断操作过电压极为严重
空母线开断并抗母线侧存在显著风险
采用断路器并抗中性点侧投切可有效治理35 kV并抗操作过电压。
Abstract
Aiming at the frequent faults of 35 kV shunt reactor in interrupting overvoltage in recent years
the few cases of faults are collected and investigated
and the fault phenomena and regularity is analyzed
the failure causes and mechanism is simulated and overvoltage control measures are studied and verified.It is found in the investigation that the switching overvoltage of 35 kV shunt reactor is very serious
remarkable risk is existed at the shunt reactor busbar side when switching no load busbar
and adoption of circuit breaker switching at the side of neutral point of shunt reactor can control the switching overvoltage very well.