Analysis on the Mixed Dual Feed-in System in Improving Wind Power Transmission Capacity
摘要
由于我国高负荷地区聚集
能源呈逆向分布
风电消纳主要以外送为主
针对风电场大量弃风的现象和高压直流输电网架的大量建设
提出了一种能够提高风电外送能力的混合双馈入直流输电系统。该系统是在传统风火联网直流外送基础上
增加风电孤岛经VSC直流外送系统
提出由短路容量比、直流最大传输功率指标与传统双馈入系统进行对比
在DIg SILENT软件中建模
结果显示了混合双馈入的优越性
最后基于故障扰动法对混合双馈入和传统双馈入的暂态特性进行对比分析
仿真结果表明混合双馈入系统能增加风电场的外送功率
故障期间VSC系统可以有效调节电网侧交流母线电压
增加LCC直流通道的外送功率。
Abstract
In this paper
a kind of mixed dual feed-in DC transmission system is proposed because of aggregation of high load area in China
reverse distribution of power and main transmission of wind power consumption and as for large number of wind abandon circumstance and large construction HVDC transmission grid. This system is based on wind and thermal interconnection DC transmission
to add wind power island through VSC DC transmission system. The comparison among short circuit capacity ratio
the maximum DC transmission power index and traditional dual feed-in system is proposed and the simulation model is set up in DIg SILENT software and the superiority of the mixed dual feed-in is shown by the result. Finally
the transient characteristics of dual and traditional feed-in based on fault disturbance method is compared and analyzed. The simulation results show that the mixed dual feed-in system can increase transmission power of wind farm
the VSC system can regulate effectively AC busbar voltage at power grid side during the fault and increase transmission power of LCC DC channel.
关键词
混合双馈入直流系统风电外送故障扰动SCR电压稳定性VSC
Keywords
mixed dual feed-in DC systemwind power transmissionfault disturbanceSCRvoltage stabilityVSC