QU XIN, WANG XINGYOU, WU XIBO, et al. Study and Prevention on Abnormal Secondary Voltage of 500 kV CVT. [J]. Power capacitor & reactive power compensation, 2017, 38(3): 105-109.
QU XIN, WANG XINGYOU, WU XIBO, et al. Study and Prevention on Abnormal Secondary Voltage of 500 kV CVT. [J]. Power capacitor & reactive power compensation, 2017, 38(3): 105-109. DOI: 10.14044/j.1674-1757.pcrpc.2017.03.019.
Study and Prevention on Abnormal Secondary Voltage of 500 kV CVT
The abnormal secondary voltage of the capacitor voltage transformer(CVT)is mainly caused by such factors as breakdown of capacitor element and short circuit of winding etc. In this paper
it is found from a real CVT which has lower secondary voltage and through related analysis that insertion of copper lead sheet in the series of the capacitor element of the product causes the connection point of outlet sheet and aluminum foil to become into a weak point. Slight change of even pole sheet structure
such as weak process control in the insertion or burr
can cause partial field strength concentrate and is easy to lead to breakdown. As for the abnormal low secondary voltage
the operation unit shall strengthen monitoring and the manufacturer is also suggested to improve the structure of outlet lead
strengthen process management and control so to prevent the similar fault and assure stable operation of power system.
关键词
电容式电压互感器(CVT)击穿故障预防
Keywords
capacitor voltage transformer(CVT)breakdownfault prevention