Influence Analysis of Electrical Equipment in the MV Distribution Network on the Transmission Feature of PLC Communication Channel
the law of influence of such primary equipment as line
distribution transformer
reactive power device and MV substation is selectively analyzed on the basis of MV distribution network channel module
which provides necessary evidence for the application of high rate narrow band PLC in the MV distribution network. It is shown by the study result that the magnitude of voltage decay increases with the increase of the length of branch line
number of branch line and the number of distribution transformer and has basically nothing to do with the length of trunk line. The mixed line of overhead and cable can cause big refraction attenuation
but the influence of MV substation on the voltage transmission decay is neglected. The reactive power device is connected to the system through a definite length of cable and the increase of compensation position and capacity will not lead to significant increase of voltage decline.
关键词
信道模型窄带电力线载波通信中压配电网传输衰耗无功补偿
Keywords
channel modelnarrowband power line carrier communicationMV distribution networktra nsmission lossreactive power compensation