SONG SHOULONG, TAN YANMIN, LI XIAOYAN. Analysis on Secondary Voltage Unbalance Fault of Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2018, 39(2): 42-43.
SONG SHOULONG, TAN YANMIN, LI XIAOYAN. Analysis on Secondary Voltage Unbalance Fault of Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2018, 39(2): 42-43. DOI: 10.14044/j.1674-1757.pcrpc.2018.02.008.
Analysis on Secondary Voltage Unbalance Fault of Capacitor Voltage Transformer
摘要
青海某变电站电容式电压互感器二次电压出现三相不平衡且波形畸变
根据故障现象采用排除法对影响互感器二次电压的各因素进行排查和仿真分析
最终检修验证了故障原因为二次回路中性线接地不良的分析结论。
Abstract
Secondary voltage unbalance and wave distortion are occurred in the capacitor voltage transformer in a certain substation in Qinghai Province. According the fault phenomenon
the elimination method is used to investigate
simulate and analyze various factors affecting the secondary voltage of the voltage transformer
finally
it is verified by the maintenance that the fault is due to bad earthing of the neutral line of the secondary circuit.
关键词
电容式电压互感器(CVT)电压不平衡波形畸变二次回路中性点
Keywords
capacitor voltage transformer(CVT)voltage unbalancewave distortionneutral point in the secondary circuit