Inter-turn Short Circuit Current Analysis for 110 kV Reactor in UHV Substation and Its Protection Improvement
摘要
分析发现某110 k V干式空心电抗器存在运行隐患
单台出现严重的匝间短路、完全烧毁
其保护也可能不动作。保护死区过大是系统中并联干式空心电抗器保护的普遍问题
本文分析了匝间故障时短路电流的影响因素
确定短路电流倍数仅与剩余电抗比和工作电压相关。提出一种基于剩余电抗比的过流保护
保护死区小
能反应轻微匝间短路。新建和改造便利
对各电压等级空心电抗器均适用。在未改造前
可在监控后台设置剩余电抗比虚遥测限额
轻微匝间短路时能及时发出报警信息
提醒运维人员检查处理。
Abstract
It is found that certain 110 k V dry-type air core reactor has hidden trouble in operation.Single unit has such problem as severe inter-turn short circuit
complete burn and no operation of its protection.Excessive protection dead zone is a common problem for shunt dry-type reactor over-current protection in system.The influence factor of short circuit current in case of inter-turn fault is analyzed
and the relationship among short circuit current factor only and residual reactance ratio and operation voltage is defined.A kind of over current protection based on residual reactance ratio with small protection dead zone and reflecting slight inter-turn short circuit.The convenience of upgrade and innovation can be applicable for air core reactor at various voltages.Before innovation
corresponding limit can be set in the substation monitoring system.Alarm information can be sent out in time to remind the operator to check and handle in case of slight inter-turn short circuit.
关键词
特高压干式空心电抗器匝间短路剩余电抗比
Keywords
ultra high voltagedry-type air core reactorinter-turn short circuitresidual reactance ratio