LI GUANGBING, PU YUXING. Study on New Harmonic Detection of Shunt Active Filter. [J]. Power capacitor & reactive power compensation, 2018, 39(4): 7-11.
LI GUANGBING, PU YUXING. Study on New Harmonic Detection of Shunt Active Filter. [J]. Power capacitor & reactive power compensation, 2018, 39(4): 7-11. DOI: 10.14044/j.1674-1757.pcrpc.2018.04.002.
Study on New Harmonic Detection of Shunt Active Filter
Such issues affecting power quality as harmonic current
load unbalance current
neutral current and low power factor etc are caused due to the increase of non-linear
unbalance load and reactive load in the distribution power grid
the shunt active power filter is normally used to achieve elimination of harmonic
reactive power compensation load unbalance current and neutral current. In the field of harmonic detection of active power filter
the shortcoming of the traditional theoretical method based on transient reactive power is analyzed
new harmonic detection method is proposed and the moving average filter(MAF) is used to replace low pass filter(LPF)for the extraction of DC component
which overcomes such defects as weak real time and dynamic of traditional detection method due to the low pass filter and
at the same time
simplifies model structure. The simulation and experimental platform is set up. It is shown by the simulation and experimental result that the new detection method has perfect detection result and superiority.
关键词
并联型有源电力滤波器非线性负载电能质量滑动平均滤波器(MAF)
Keywords
shunt active power filternonlinear loadspower qualitymoving average filter(MAF)