CHEN LING, WANG JINGBAO, LIU RUI, et al. Partial Discharge Detection Method of Dry-type Air-core Reactor Based on Oscillation Wave. [J]. Power capacitor & reactive power compensation, 2019, 40(1): 92-96.
CHEN LING, WANG JINGBAO, LIU RUI, et al. Partial Discharge Detection Method of Dry-type Air-core Reactor Based on Oscillation Wave. [J]. Power capacitor & reactive power compensation, 2019, 40(1): 92-96. DOI: 10.14044/j.1674-1757.pcrpc.2019.01.017.
Partial Discharge Detection Method of Dry-type Air-core Reactor Based on Oscillation Wave
Dry-type air-core reactor plays an important role in regulating reactive power of grid.However
during the operation period of the reactor
the short circuit fault can caused by such reasons as aging of insulation material
partial over heat etc
resulting in serious accident and causing huge economic losses.At present
the insulation performance detection method of the air-core reactor is to judge whether the reactor has fault by way of comparing both decay and frequency variation of the voltage oscillation wave on both sides of the reactor which is caused by the inductance variation of the reactor.In this paper
the parameters of oscillation circuit is determined by setting up the simulation model of the oscillation wave system so to detect the partial discharge during the oscillation period
in which the partial discharge detection contains such method as ultra-high frequency method
high frequency method
pulse current method and ultrasonic method as well as comprehensive detection.It is shown by the test that the potential fault of the air core reactor can be found and the occurrence of malignant accident can be avoided.