ZHOU XIU, TIAN TIAN, LUO YAN, et al. Analysis on Heating Problem of Dry-type Reactor Earthing System and Foundation. [J]. Power capacitor & reactive power compensation, 2019, 40(6): 73-78.
ZHOU XIU, TIAN TIAN, LUO YAN, et al. Analysis on Heating Problem of Dry-type Reactor Earthing System and Foundation. [J]. Power capacitor & reactive power compensation, 2019, 40(6): 73-78. DOI: 10.14044/j.1674-1757.pcrpc.2019.06.014.
Analysis on Heating Problem of Dry-type Reactor Earthing System and Foundation
Regarding the earthing system and foundation heating problem of 66 kV dry-type hollow reactor in a 750 kV substation
in order to accurately analyze the reason and take corresponding measures
firstly infrared temperature measurement was used to identify and determine the source of heat
then
we replaced the grounding system metal
analyzed structure of the reactor infrastructure
tested the conducting performance of steel reinforcement inside the foundation
simulated the earthing system of the reactor
analyzed the effects of circulation heating and eddy current heating comprehensively
the causes of fever were identified and corresponding measures were put forward. Finally
it was concluded that the eddy current of the conductive material in the magnetic field was the cause of the heating of the flat iron grounded in the reactor
the heating of the reactor base was caused by the metal ring in the raft.
关键词
干式电抗器接地红外测温涡流环流
Keywords
dry-type reactorearthinginfrared temperature measurementeddy currentloop current