HE YINGJING, LI JIHONG, DAN YANGQING, et al. Study on Performance Improvement of Multiple DC Infeed Systems by MMC-HVDC System. [J]. Power capacitor & reactive power compensation, 2020, 41(3): 106-111.
HE YINGJING, LI JIHONG, DAN YANGQING, et al. Study on Performance Improvement of Multiple DC Infeed Systems by MMC-HVDC System. [J]. Power capacitor & reactive power compensation, 2020, 41(3): 106-111. DOI: 10.14044/j.1674-1757.pcrpc.2020.03.018.
Study on Performance Improvement of Multiple DC Infeed Systems by MMC-HVDC System
MMC-HVDC can provide voltage support for the receiving power system.The multiple infeed interaction factor(MIIF) between the converter buses can be reduced in a multiple DC infeed system by the connection of the MMC-HVDC system
thus the multiple infeed effective short circuit ratio(MIESCR)of the converter bus can be increased and the stability of the multiple DC infeed system can be improved.However
this improvement is related to the operation mode and the connection location of the MMC.Therefore
it is important to study the proper operation mode and the connection location of the MMC.The calculation formula which shows the improvement of the MIIF by the MMC-HVDC connection is obtained based on the nodal impedance matrix.From the formula the best operation mode and connection location of the MMC station is given.Then
the correctness of the calculation formula is verified by a typical study case.Finally
the improvement of the transient stability by the MMC connection is verified by the simulation of Zhejiang power grid.
关键词
直流多馈入输电系统多馈入相互作用因子MMC接入位置
Keywords
multiple DC infeed systemmultiple infeed interaction factorMMC station location