LIN ANNI, HUANG YONGZHANG, LIN WEIFANG, et al. Comparison of Suppression Effect of Different Dynamic Reactive Power Compensation Devices for Transient Overvoltage Caused by HVDC System Faults. [J]. Power capacitor & reactive power compensation, 2020, 41(4): 116-122.
LIN ANNI, HUANG YONGZHANG, LIN WEIFANG, et al. Comparison of Suppression Effect of Different Dynamic Reactive Power Compensation Devices for Transient Overvoltage Caused by HVDC System Faults. [J]. Power capacitor & reactive power compensation, 2020, 41(4): 116-122. DOI: 10.14044/j.1674-1757.pcrpc.2020.04.021.
Comparison of Suppression Effect of Different Dynamic Reactive Power Compensation Devices for Transient Overvoltage Caused by HVDC System Faults
The high-voltage withstand capability of renewable energy units is poor
and the transient overvoltage at the sending end caused by HVDC faults is easily transmitted to the nearby wind farms
leading to wind turbine tripping accidents.In terms of the measures of suppressing transient overvoltage by installing dynamic reactive power compensation devices at the sending end
the suppression effects of commonly used dynamic reactive power compensation devices are compared in a simple two-region system based on electro?magnetic transient simulation.The results show that the synchronous compensator has the best suppression effect on the transient overvoltage of the renewable energy HVDC delivery system.Then
the conclusion of the two-region system is verified in an actual large-scale power grid example based on the electromechanical transient simulation.Finally
the suppression effect of key performance parameters of synchronous condenser on transient overvoltage is discussed.By optimizing the d axis transient reactance and transient time constant
the transient voltage rise can be improved.
关键词
动态无功补偿同步调相机暂态过电压换相失败直流闭锁
Keywords
dynamic reactive power compensationsynchronous condensertransient overvoltagecommutation failureHVDC block