MA ZHIQUAN, XU QUNWEI, LYU WENTAO, et al. Test on High Order Harmonics of Long Cable Connection Point of MMC Under Isolated Island. [J]. Power capacitor & reactive power compensation, 2020, 41(4): 145-151.
MA ZHIQUAN, XU QUNWEI, LYU WENTAO, et al. Test on High Order Harmonics of Long Cable Connection Point of MMC Under Isolated Island. [J]. Power capacitor & reactive power compensation, 2020, 41(4): 145-151. DOI: 10.14044/j.1674-1757.pcrpc.2020.04.026.
Test on High Order Harmonics of Long Cable Connection Point of MMC Under Isolated Island
MMC is the core equipment of energy conversion of flexible DC distribution grid and AC power grid.The quality of converter under normal operation is verified by the power quality test at the AC interconnection point of the converter.However
in case of weak grid operation condition at isolated island mode
the AC interconnection point through long distance cable interconnection has high order harmonic resonance phenomena
which degrades seriously voltage waveform.In this paper
small coefficient mathematical model for converter-long cable-load system is set up and the intrinsic mechanism of high frequency harmonic transmission is studied.The Numerical analysis is performed by such Python open source software package as Numpy and Scipy etc.It is verified that the necessary prerequisites for the occurrence of high frequency resonance is the weak power grid.The characteristic equation of long cable and weak grid of inherent resonance frequency is deduced and solved.The rule that the increase resonance frequency of the impedance of bridge arm reactor reduces with the increase of cable length.The theoretical calculation result and the actual measurement result are basically identical.The MMC inverter with long cable interconnection is suggested and high frequency filter is mounted on opposite side of cable to suppress harmonic amplification of weak grid in operation.
关键词
模块化多电平换流器(MMC)现场测试高次谐波孤岛方式柔性直流配电网
Keywords
modular multilevel converter(MMC)site testhigh order harmonicsisolated island modeflexible DC distribution
Issue on Reactor Current Stability in Complete Harmonic Condition
Influence of Modular Multilevel Converter Circulating Current Control on Output Voltage Harmonics of Converter for Luxi Asynchronous Interconnection Project
Research on Reactive Power Compensation Control Strategy Based on Modular Multilevel Converter
Site Test and Analysis of Harmonic Emission Characteristics of DC Chargers for Electric Vehicles
Related Author
ZHAO Da
LIANG Cong
CHEN Shao-bin
ZHOU Jingyu
YANG Fan
REN Chenglin
GOU Ruifeng
REN Junhui
Related Institution
Guilin Power Capacitor Co.,Ltd.
CSG EHV Power Transmission Company
Xi’an XD Power System Co.,Ltd.
Department of Development Planning,State Grid Beijing Electric Power Company
School of Electric Power,South China University of Technology