Comparative Study on DC Fault Ride-through Performances of Flexible HVDC Systems Under Four Typical DC Fault Clearance Schemes
the main problem of flexible high voltage direct current(HVDC) system based on modular multilevel converter(MMC) is the DC fault clearance schemes.At present
academic and industrial circles have proposed a variety of flexible HVDC systems with DC fault clearance capability.In order to better understand the advantages and disadvantages of these flexible HVDC systems
it is necessary to analyze their DC fault clearance characteristics.For the four typical flexible HVDC systems with DC fault clearance capability
the paper analyzes and compares their DC fault ride-through performances.Firstly
this paper summarizes four typical DC fault clearance configurations including the DC circuit breaker(DCCB)
the hybrid MMC with full bridge submodules and half bridge submodules(FHMMC)
the LCC-MMC hybrid configuration with diode groups installed in the DC line close to the converters(LCC-D-MMC) and the hybrid topology with an LCC and an MMC in series-connection.Then
the basic structure
control mode and fault clearance schemes of the four configurations based flexible HVDC systems are discussed.Finally
a three-terminal simulation model is built to compare the DC fault clearance characteristics of the four flexible HVDC systems.The simulation result shows that the DCCB can isolate DC faults quickly and selectively
and the DCCB based flexible HVDC system performs the best DC fault clearance characteristics.Considering the cost efficiency and operation flexibility
the LCC-MMC hybrid topology has certain value of practic al applic ation in engineering.