Analysis on Abnormal Unbalanced Current of AC Filter Capacitor of Converter Station Based on PSCAD/EMTDC
摘要
交流滤波器作为直流输电系统的重要组成部分
其运行工况直接影响着直流输电系统功率传输
本文结合交流滤波器实际运行经验
对交流滤波器C
1
电容器不平衡异常进行分析
总结出交流滤波器C
1
电容器不平衡故障主要为电容器本体故障和层间放电故障
并通过PSCAD/EMTDC仿真软件对故障原因进行研究分析验证
提出了C
1
电容器本体故障及层间放电故障的改善措施
对换流站交流滤波器的安全运行有着现实意义。
Abstract
The operation condition of AC filter
an important part of DC transmission system
affects directly power transmission of the HVDC power transmission. In this paper
the unbalance abnormality of C
1
capacitor of AC filter is analyzed with combination of the actual operation experience of AC filter
finding the unbalance fault of C
1
capacitor of AC filter is due to both capacitor proper and inter-layer discharge. The cause of the fault is analyzed
studied and verified by the PSCAD/EMTDC simulation software and the improvement measures for the fault of capacitor proper and inter-layer discharge is proposed
which has a practical significance to the safe operation of AC filter in the converter station.
关键词
PSCAD/EMTDC换流站交流滤波器C1电容器不平衡电流层间放电
Keywords
PSCAD/EMTDCconverter stationAC filter capacitorunbalanced current of C1 capacitorinterlayer discharge