LIU ZHIHAO, SU SHIPING, TANG MOYI, et al. Shunt Loop Current Suppression Method of Intermittent Power Grid Networking-multi-inverter Based on Hybrid Automata Theory. [J]. Power capacitor & reactive power compensation, 2021, 42(1): 128-135.
LIU ZHIHAO, SU SHIPING, TANG MOYI, et al. Shunt Loop Current Suppression Method of Intermittent Power Grid Networking-multi-inverter Based on Hybrid Automata Theory. [J]. Power capacitor & reactive power compensation, 2021, 42(1): 128-135. DOI: 10.14044/j.1674-1757.pcrpc.2021.01.021.
Shunt Loop Current Suppression Method of Intermittent Power Grid Networking-multi-inverter Based on Hybrid Automata Theory
In view of such problem as outstanding of loop current and difficult suppression of intermittent power supply grid-connected multi-inverter in parallel operation
in this paper
the hybrid automatic machine theory to suppress the parallel power supply of the intermittent power supply grid-connected multi-inverter is proposed. Firstly
the hybrid characteristics and the principle of circulating current generation of parallel power supply grid-connected multi-inverters in parallel are analyzed in detail and the mathematical relationship between inverter output voltage and circulating current size is obtained. Then the in-depth study of the principle and method of parallel power supply multi-inverter parallel operation loop control using hybrid automatic machine theory modeling and control is carried out. According to the relationship between the working state of the switching device and the output voltage of the inverter
multiple inverters are connected in parallel. Finally
the simulation is verified by the matlab simulation platform. It is shown by the simulation result that the correctness and feasibility of the loop controller and the corresponding loop suppression method designed in this paper can achieve better circulation control effect by using the hybrid automata model
which can effectively suppress the circulation between multi-parallel inverters.
关键词
环流并联运行混成自动机混成控制
Keywords
loop currentparallel operationhybrid automatahybrid control