ZOU XIN, LI HUI, ZHAO SHENGKAI, et al. Study on High Voltage Ride-through Control Strategy of Direct-drive Wind Farm. [J]. Power capacitor & reactive power compensation, 2021, 42(1): 191-198.
ZOU XIN, LI HUI, ZHAO SHENGKAI, et al. Study on High Voltage Ride-through Control Strategy of Direct-drive Wind Farm. [J]. Power capacitor & reactive power compensation, 2021, 42(1): 191-198. DOI: 10.14044/j.1674-1757.pcrpc.2021.01.030.
Study on High Voltage Ride-through Control Strategy of Direct-drive Wind Farm
The harm of high voltage fault of power grid to the safe and stable operation of new energy sets and power grid is becoming more and more serious. Firstly
this paper introduces the current national high voltage ride through(HVRT)standards and analyzes the typical causes of high voltage faults in the power grid. According to the different causes and degree of fault
the high voltage fault can be divided into two categories. Secondly
the permanent magnet direct driven wind turbine(PMSG)is taken as an example
the transient transition process of PMSG during the high voltage fault is analyzed and the high voltage ride through control strategy is designed. It is shown by the analysis that under the typical parameter design it is difficult for PMSG to pass through the deep high voltage fault caused by DC transmission system blocking.Furthermore
the coordinated control strategy of new energy unit and reactive power compensation device is proposed to realize the ride through of new energy unit under deep high voltage fault. Finally
the analysis results and the effectiveness of the proposed method are verified on the basis of PSCAD/EMTDC electromagnetic transient simulation.
关键词
直驱风电机组高电压穿越无功补偿装置
Keywords
PMSGhigh voltage ride-throughreactive power compensation equipment