WEI HUANGLI, CAO WEI, HUANG RUANMING, et al. Problems Existing in Simplification of Network Wiring and Analysis of Its Influence on Selection of Neutral Point Reactor of Main Transformer. [J]. Power capacitor & reactive power compensation, 2021, 42(5): 173-179. DOI: 10.14044/j.1674-1757.pcrpc.2021.05.028.
Problems Existing in Simplification of Network Wiring and Analysis of Its Influence on Selection of Neutral Point Reactor of Main Transformer
In view of such present situation that the load is put on a higher voltage level in the short-circuit current simulation calculation of the power system
the network wiring of 2~3 voltage level in the study network is only retained and simplification of the network will certainly cause incomplete zero sequence path. First
the problem after simplifying the zero-sequence path is analyzed. Then
the influence on selection of neutral point reactor of main transformer after simplifying the zero-sequence path is analyzed. The analysis of the calculation example shows that for the nodes where the single-phase grounding short-circuit current is on the verge of exceeding the standard and needs to be accurately calculated
the incomplete zero-sequence path will bring uncertainty factor to the calculation result of single phase grounded short circuit current of the planned network and the selection of grounded small reactance of the neutral point of 500 kV main transformer. Therefore
it is necessary to improve the network wiring of the 1 to 2 voltage levels for the lowerlevel networks of these nodes so to make the calculation results of the bus single-phase grounding short-circuit current more accurate.
关键词
零序通路网络接线简化等值单相接地短路
Keywords
zero sequence pathnetwork wiringsimplified equivalentsingle-phase grounding short circuit