ZHANG YINLIANG, ZHAO NANLAI. Abnormal Analysis of Power Factor Type Controller in Parallel Operation with Transformer. [J]. Power capacitor & reactive power compensation, 2014, 35(5): 96-99.
ZHANG YINLIANG, ZHAO NANLAI. Abnormal Analysis of Power Factor Type Controller in Parallel Operation with Transformer. [J]. Power capacitor & reactive power compensation, 2014, 35(5): 96-99. DOI: 10.14044/j.cnki.dldrq.2014.05.019.
Abnormal Analysis of Power Factor Type Controller in Parallel Operation with Transformer
摘要
针对变压器并列运行过程中功率因数型控制器出现超前状态以及变压器发热严重的情况进行分析
通过计算变压器并列运行后的循环电流
并比较不同类型控制器的原理及优缺点
发现两台变压器的分接开关档位不一致
并列运行后
其产生的循环电流是导致功率因数型控制器出现异常的原因。同时根据控制器的性能
提出采用低压无功功率型控制器的建议
供相关企业工作人员参考。
Abstract
In this paper
the leading condition of power factor type controller and the serious heat of transformer during parallel operation of the transformer are analyzed. The inconsistency of tap changers of two sets of transformers is found out by way of calculating loop current after parallel operation of transformer and of comparing principles
advantages and disadvantages of differ types of controllers. The abnormal reason of power factor type controller is from the loop current after parallel operation. At the same time
such suggestion as adoption of low voltage reactive power type controller is proposed in accordance with performance of the controller as reference for relevant enterprises staffs.
关键词
功率因数型控制器变压器并列运行分接开关循环电流
Keywords
power factor controllerparallel operation with transformertap changerloop current