ZHAO RU-GUO. Filed Measurement of Capacity and Dielectric Loss on Site for the TEHMP-500 Type 500kV Capacitive Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2007, (3): 46-47.
ZHAO RU-GUO. Filed Measurement of Capacity and Dielectric Loss on Site for the TEHMP-500 Type 500kV Capacitive Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2007, (3): 46-47.DOI:
a grounding-switch is set in the front of the middle transformer primary turn.During measurement on site
the front of the middle transformer primary turns becomes on grounding through operating the outside handle to close the grounding-switch.Thus the capacitances of C13 and C2 and dielectric loss can be measured conveniently using inverse connecting method
the disadvantages of self-excitation method can be avoided.