LIU YANG, WEI FENG, NIE ZHI-QIANG, et al. Seismic Test on 500kV Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2010, 31(4): 42-46.
LIU YANG, WEI FENG, NIE ZHI-QIANG, et al. Seismic Test on 500kV Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2010, 31(4): 42-46. DOI: 10.14044/j.1674-1757.pcrpc.2010.04.009.
500kV电容式电压互感器抗震试验
摘要
通过对出口美国洛杉矶水电站的500 kV电容式电压互感器(CVT)实型模拟抗震试验
对其抗震性能提出了初步评价。抗震试验采用电磁振动台
对试品分别输入连续正弦波和正弦共振波
在实际地震波对CVT各组部件在地震加速度5 m/s2规定的地震裂度下
其各性能参数满足美国标准及技术协议的要求
为高电压的CVT抗震设计提供了参考。
Abstract
The preliminary evaluation of the seismic performance of 500 kV capacitor voltage transformer exported to the hydropower station in Los Angeles of America is made through simulation of seismic test on the actual model.The continuous sine wave and sine-wave resonance are input respectively on the prototype through the electromagnetic vibration table.At specified 5 m/s2 earthquake intensity imposed on each set of component of capacitor voltage transformer
each performance parameter meets American standards and the requirements of technical agreement
that can provide a reference for the seismic design of high voltage capacitor voltage transformer.