YANG YANG, XU QIANG, QIN WEI, et al. Diagnosis and Analysis of a Fault of 500 kV Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2011, 32(4): 68-71.
YANG YANG, XU QIANG, QIN WEI, et al. Diagnosis and Analysis of a Fault of 500 kV Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2011, 32(4): 68-71. DOI: 10.14044/j.1674-1757.pcrpc.2011.04.014.
As for the secondary protection action caused by instable rise of secondary voltage of phase A of 500 kV capacitor voltage transformer(CVT)
it is found through diagnosis and test of phase A of CVT that the dielectric loss factor
the dielectric resistance and capacitance of the upper coupling capacitor segment are severely unqualified.It is pointed in the preliminary analysis that the failure of seal cover gradually leads to inner damp
causing break-down or short-circuit of some inner capacitance sections.According to disassembly inspection
it is proved that un-tight sealing cover leads to moisture in such batch of CVT in 1 year’s continuous operation and the trace of breakdown or short-circuit of some capacitance sections exists.It is pointed out in the analysis that the breakdown or short-circuit of some capacitance sections causes the change of voltage ratio
which rises the secondary voltage and leads to the protection action.
关键词
电容式电压互感器(CVT)介损绝缘电阻电容器元件分压比
Keywords
capacitor voltage transformer(CVT)dielectric lossdielectric resistancecapacitor elementvoltage division ratio