HUANG BIN, SU WEN-YU, LIU XIAO-BO, et al. Analysis and Design Modification on Overheating in the Connected Component of Capacitor. [J]. Power capacitor & reactive power compensation, 2012, 33(3): 40-43.
HUANG BIN, SU WEN-YU, LIU XIAO-BO, et al. Analysis and Design Modification on Overheating in the Connected Component of Capacitor. [J]. Power capacitor & reactive power compensation, 2012, 33(3): 40-43. DOI: 10.14044/j.1674-1757.pcrpc.2012.03.009.
TBB24-35-60120/334-2BLW capacitor installations are widely used in Jiangxi Province 500 kV substations.The structural defects in the connected component of this type of capacitor banks always cause overheating fault in the connected component of capacitor.To guarantee the safety of power grid
the internal structure of this connected component of capacitor is analyzed
a new type of connected component is designed and used successfully at site.It is suggested to use 50 mm2 BV cables instead of the original 35 mm2 soft copper cable and SBK-1-M16 special transformer clamp instead of original lead connector.And the trap in lead installation shall be maintained.