WANG BO, HUANG YANGUANG, YI LU, et al. Preliminary Study on the Preventive Test of Transformer Neutral DC Current Blocking Device. [J]. Power capacitor & reactive power compensation, 2015, 36(1): 57-60.
WANG BO, HUANG YANGUANG, YI LU, et al. Preliminary Study on the Preventive Test of Transformer Neutral DC Current Blocking Device. [J]. Power capacitor & reactive power compensation, 2015, 36(1): 57-60. DOI: 10.14044/j.1674-1757.pcrpc.2015.01.013.
When the DC current flows into inside of transformer
it will cause DC bias of transformer
and such problems as big noise and increase of reactive power loss. Various problems brought by the DC current into the transformer can be reduced by way of adding the blocking device in the neutral point of transformer
but the problem is how to perform the preventive test to the device. The preventive test items for the device is set up in accordance with field experience and the blocking device for 13 units of transformers operated at Guangzhou grid is inspected and the fault as well as hidden trouble are found. Verification of preventive test has a definite practical value and reference.
关键词
直流偏磁变压器中性点隔直装置预防性试验
Keywords
DC biastransformer neutralDC current blocking devicepreventive test