QIAO YAJUN, LIN QIXIONG, LIN LIBO. Overheat Defect Analysis and Treatment on Electromagnetic Unit of 500 kV CVT. [J]. Power capacitor & reactive power compensation, 2015, 36(4): 61-63.
QIAO YAJUN, LIN QIXIONG, LIN LIBO. Overheat Defect Analysis and Treatment on Electromagnetic Unit of 500 kV CVT. [J]. Power capacitor & reactive power compensation, 2015, 36(4): 61-63. DOI: 10.14044/j.1674-1757.pcrpc.2015.04.013.
500kV CVT电磁单元过热缺陷分析与处理
摘要
通过红外测温发现电容式电压互感器电磁单元异常发热后
对其进行检查发现中间变压器端子盒存在进水、锈蚀现象
二次端子绝缘电阻降低。通过结合现场情况、仿真分析、试验等方法
发现设备密封性能不良主要由密封胶条安装质量不良与密封盖板受力不均两个原因造成。针对缺陷原因
制定了排除同类设备隐患、改进设备密封结构、加强运行监测与设备验收等措施
有效保证设备安全稳定运行。
Abstract
The electromagnetic unit of capacitor voltage transformer is checked by the infrared temperature measurement after its abnormal heat and found such circumstance as water penetration and rust in the intermediate transformer
dielectric resistance reduction of secondary terminal. It is found through site situation
simulation analysis and test etc
that the weak sealing is due to bad installation quality of the sealing strip and uneven force of the sealing cover. As for the reason of the defects
such effective measures as eliminating hidden danger of similar equipment
improving the sealing structure of equipment
strengthening operation monitoring and equipment acceptance are formulated
which assures effectively safe and stable operation of equipment.
关键词
电容式电压互感器(CVT)红外测温中间变压器密封性能
Keywords
capacitor voltage transformer(CVT)infrared temperature measurementintermediate transformersealing performance