the capacitor is used as the sensor. The capacitor has temperature drift characteristic
which leads to capacitance variation
and then change voltage division ratio and ultimately affect the accuracy. Accuracy test is performed with the power frequency test transformer before delivery of the product. However
the power is only supplied by the cascade resonant transformer at site installation and the accuracy can also be affected by the different frequencies. In addition
the voltage division variation is led by the injected impedance of the primary equipment. The accuracy can also be affected by the size of high voltage wire and the included angle between the high voltage wire and porcelain. For above reason
unqualified accuracy of CVT often occurs in the acceptance check. In this paper
each influence feature is analyzed and precautions at site are summarized through calculation and actual experience.