CHANG PENG, ALIMJAN·KADER, WANG HAIYUN. Study on Protection of Neutral Point Earthing Capacitance of Converter Transformer by Spark Gap. [J]. Power capacitor & reactive power compensation, 2016, 37(1): 56-60.
CHANG PENG, ALIMJAN·KADER, WANG HAIYUN. Study on Protection of Neutral Point Earthing Capacitance of Converter Transformer by Spark Gap. [J]. Power capacitor & reactive power compensation, 2016, 37(1): 56-60. DOI: 10.14044/j.1674-1757.pcrpc.2016.01.012.
火花间隙对保护换流变压器中性点接地电容的研究
摘要
高压系统中直流偏磁对换流变压器和交直流输电产生巨大的危害
限流和隔直是抑制直流偏磁的主要方法
目前广泛采用的是通过中性点串联电容的方法
对电容的保护研究很少。本文利用PSCAD/EMTDC建立500 k V的高压直流输电电磁暂态仿真平台
在发生工频过电压时
对换流变压器中性点处串联电容的过电压
以及其2端保护装置火花间隙进行了仿真和分析
选择了最佳容抗值的电容器
并探究了火花间隙对中性点串联电容器的保护
结果表明:火花间隙对换流变压器中性点接地电容以及变压器中性点起到保护作用。
Abstract
In high voltage system
a great harm is caused to the converter transformer and AC and DC power transmission by the DC biasing. The main method to suppress the biasing is current limiting and blocking.At present
the widely used method is series capacitance through the neutral point
but there is little research on the protection of the capacitor. In this paper
the electromagnetic transient simulation platform for 500 k V HVDC is set up by PSCAD/EMTDC
and in case of power frequency overvoltage
the overvoltage of the series capacitor at the neutral point of converter transformer
and also the spark gap of the protection device on both sides are simulated and analyzed
the capacitor with the most ideal capacitive reactance is selected
and the protection of spark gap to the neutral point series capacitor is also discussed. It is shown by the result that the spark gap has the protection function to the neutral point earthing capacitor of converter and the neutral point of transformer.
关键词
高压系统直流偏磁工频过电压火花间隙
Keywords
high voltage systemDC biasingpower frequency overvoltagespark gap