LI ZIMING, YAO XIUPING, WANG HAIYUN, et al. Study on Reactive Power Control Strategy of VMP System for Wind Farm. [J]. Power capacitor & reactive power compensation, 2016, 37(2): 67-71.
LI ZIMING, YAO XIUPING, WANG HAIYUN, et al. Study on Reactive Power Control Strategy of VMP System for Wind Farm. [J]. Power capacitor & reactive power compensation, 2016, 37(2): 67-71. DOI: 10.14044/j.1674-1757.pcrpc.2016.02.014.
as a new energy power generation technology at present
is a kind of power generation mode with most matures and scales
which at the time of bringing fast development of electric power industry in China
also bringing many difficulties in voltage regulation in the power grid. The operation difficulty is increased due to intensive operation of a large number of dynamic reactive power compensation devices
lack of coordination and continuous appearance of new problem. As for the voltage control issue of wind farm after operation
the advantage and disadvantage of presently existing reactive voltage management control system of wind power plant is analyzed through its study
the reactive power/voltage control measures based on hierarchical management is proposed further
the hierarchical control strategy of reactive voltage of wind farm is embedded into the reactive power /voltage automatic control platform(VMP)of wind power plant to make an appropriate adjustment of wind turbine unit of wind power plant
substation
reactive compensation equipment(SVC/SVG)and main transformer tap of booster station and apply the reactive power control strategy into certain wind power plant in Xinjiang for site test. It is shown by the verification result that the proposed reactive power strategy of wind power plant can adjust the voltage of wind power plant
control effectively reasonable flow of reactive power of power network
optimize power load distribution inside the power network and assure safe
stable and economic operation of power grid.
关键词
风电场VMP系统无功控制控制策略
Keywords
wind farmVMP systemreactive power controlcontrol strategy