LI BICHUN, SONG SHOULONG. Influence of Ground Insulation Resistance of Medium Terminal of Capacitive Divider on tanδ Measurement. [J]. Power capacitor & reactive power compensation, 2018, 39(6): 71-74.
LI BICHUN, SONG SHOULONG. Influence of Ground Insulation Resistance of Medium Terminal of Capacitive Divider on tanδ Measurement. [J]. Power capacitor & reactive power compensation, 2018, 39(6): 71-74. DOI: 10.14044/j.1674-1757.pcrpc.2018.06.014.
电容分压器中压端对地绝缘电阻对tanδ测量值的影响
摘要
在对电容分压器的tanδ测试中
有时会出现高压电容和中压电容的tanδ在正常的范围内
而总电容tanδ明显偏小甚至为负值的现象。针对这种异常情况
通过建立电容分压器中压端对地模型
分析确定了电容分压器中压端对地绝缘电阻对tanδ测量值的函数关系
并在实际的电容分压器产品上模拟试验
验证分析的正确性
为处理此类电容分压器tanδ异常的情况提供参考。
Abstract
In the measurement of tanδ test of capacitive voltage divider
such phenomena as tanδ of high voltage and medium voltage capacitors is sometimes in the normal range but total capacitance tanδ is obviously smaller or even negative. In view of this abnormal situation
the function relation of ground insulation resistance of medium terminal of capacitive divider to the tanδ measurement is analyzed and determined byway of establishing ground model of medium terminal of capacitive divider. The simulation test is per-formed on the actual capacitive divider to verify and analyze its correctness
which can provide referencefor the abnormal tanδ of such capacitive divider.
关键词
电容分压器中压端对地绝缘电阻电容tanδ
Keywords
capacitive divider medium voltageground insulation resistancecapacitancetanδ