TAN MING, LIAO MINGYANG, SHI JIAN, et al. Analysis and Improvement of Switching Control Logic Defect for AC Filter in Yunnan—Guangdong UHVDC System. [J]. Power capacitor & reactive power compensation, 2019, 40(3): 29-33.
TAN MING, LIAO MINGYANG, SHI JIAN, et al. Analysis and Improvement of Switching Control Logic Defect for AC Filter in Yunnan—Guangdong UHVDC System. [J]. Power capacitor & reactive power compensation, 2019, 40(3): 29-33. DOI: 10.14044/j.1674-1757.pcrpc.2019.03.006.
AC filter is important equipment in the converter station of ±800 kV Yunnan—Guangdong ultra-high voltage direct current(UHVDC)transmission system
with such features as large capacity and frequentswitching
and its switching control logic affects directly safe and stable operation of the DC transmission system. In this paper
two abnormal events are analyzed: rise of AC busbar voltage due to abnormal operation of group filter with thermal stand by condition and power limitation due to undefined group filter blade. And this issue that the operated group filters has no way to remove automatically after the tripping of the line circuit breaker is discussed. In view of the control logic defect of them
corresponding improvement suggestion and proposal are propped
which provides reference for the design and operation of actual DC engineering.