CHEN XUBIN. Cause Analysis on Low Secondary Voltage of Capacitor Voltage Transformer in Pumped Storage Power Station. [J]. Power capacitor & reactive power compensation, 2019, 40(3): 101-104.
CHEN XUBIN. Cause Analysis on Low Secondary Voltage of Capacitor Voltage Transformer in Pumped Storage Power Station. [J]. Power capacitor & reactive power compensation, 2019, 40(3): 101-104. DOI: 10.14044/j.1674-1757.pcrpc.2019.03.019.
the faultof low secondary voltage of capacitor voltage transformer(CVT)in pumped storage power station is introduced firstly. The analysis and calculation is performed according to the structure feature and operating principle of the capacitor voltage transformer
judging preliminarily that the fault is due to breakdown capacitive component of the capacitor voltage transformer. It is found after disassembly inspection and test analysis of the equipment that four capacitive elements are breakdown. The correctness of the analysis is proved
the fault is found out
the fault is eliminated and power supply is recovered after replacement with new capacitor voltage transformer and the secondary power supply is recovered. Finally
the suggestion and preventions are proposed to the operation and manufacturer for reference.