ZHANG JINXIANG, WANG XIANGFENG, LI ZHENDONG, et al. Fault Location Algorithm for Double-star-connection Shunt Capacitor Banks. [J]. Power capacitor & reactive power compensation, 2019, 40(5): 20-24.
ZHANG JINXIANG, WANG XIANGFENG, LI ZHENDONG, et al. Fault Location Algorithm for Double-star-connection Shunt Capacitor Banks. [J]. Power capacitor & reactive power compensation, 2019, 40(5): 20-24. DOI: 10.14044/j.1674-1757.pcrpc.2019.05.004.
Shunt capacitors have always been the equipment with high failure rate in substation
while there are dozens of capacitors in a group of capacitors and a large number of series and parallel elements inside each capacitor
which makes it very difficult for the capacitor bank to quickly and accurately locate the fault. In this paper
a fault location algorithm based on neutral line unbalanced current is proposed for the application of double wye connection in shunt parallel capacitor banks. At the same time
considering the difference between the fused and fuseless capacitor
the derivation is made respectively. The simulation model established by PSCAD and Matlab is used to verify the feasibility of the algorithm proposed by the capacitorunitinthecaseofsinglefault
multiple fault and continuous fault of the unit.
关键词
并联电容器组双星形接线故障定位中性线不平衡电流
Keywords
shunt capacitor banksdouble-star-connectionfault locationneutral line unbalanced current