WU BIN, CHEN YEQIANG. Discussion on Application and Problems of Automatic Voltage Control in Large Nuclear Power Plant. [J]. Power capacitor & reactive power compensation, 2021, 42(3): 44-49.
WU BIN, CHEN YEQIANG. Discussion on Application and Problems of Automatic Voltage Control in Large Nuclear Power Plant. [J]. Power capacitor & reactive power compensation, 2021, 42(3): 44-49. DOI: 10.14044/j.1674-1757.pcrpc.2021.03.007.
the application of automatic voltage control(AVC)in large-scale nuclear power plant is introduced. The working principle of AVC in power plant is described in detail from such aspects as system principle
system structure
reactive power distribution principle
substation adjustment strategy and logic locking etc. According to the special situation of large nuclear power plant
the problems of AVC in the actual operation process are analyzed. In view of the issue of matching the AVC with the automatic excitation regulator(AVR)
the measures to modify the AVC setting have been taken as for the problem of non-triggering alarm due to abnormal bus bar voltage and of the lack of data lock without refresh in the background control logic
the measures on adding related control logic in AVC background are adopted. In view of such issue as frequently triggering DCS magnetic latching alarm
the measures to modify the DCS logic are proposed. Both reliability and stability of AVC system are improved through the summarization of AVC application and and solution to the existed problems
which provide assurance for safe and stable operation of power system and
at the same time
provide valuable operation experience for the same type of nuclear power plant.
关键词
自动电压控制(AVC)控制策略逻辑报警措施
Keywords
automatic voltage control(AVC)control strategylogicwarningmeasures