LI WEI, ZHANG WENMING, DONG QUAN, et al. Analysis and Treatment on Short Circut Fault of 66 kV Dry-type Air-core Reactor. [J]. Power capacitor & reactive power compensation, 2021, 42(3): 50-55.
LI WEI, ZHANG WENMING, DONG QUAN, et al. Analysis and Treatment on Short Circut Fault of 66 kV Dry-type Air-core Reactor. [J]. Power capacitor & reactive power compensation, 2021, 42(3): 50-55. DOI: 10.14044/j.1674-1757.pcrpc.2021.03.008.
66 kV干式空心电抗器短路故障的分析与处理
摘要
本文介绍了66 kV干式空心电抗器的短路故障情况
依据其结构特点及现场检查
初步判断第7、8绕包封层间绝缘击穿。对该设备解体检查分析
发现包封层表面鸟类排泄物、毛絮等积污明显
有沿鸟类排泄物的爬电痕迹
第7、8绕包封层存在贯穿性过火过烟痕迹
其包封内各层导线有不同程度烧蚀
烧蚀点附近导线包覆绝缘膜韧性良好。推断包封层表面积污发生污湿放电
逐渐累积恶化后损坏包封股间、层间绝缘
导致电抗器短路。据此
提出检查电抗器防腐蚀涂层
例行检修增加通风道清理项目
改造电抗器格栅
增强防鸟性能等运检预防措施
以保障设备安全运行。
Abstract
The short circuit fault of 66 kV dry-typeair-core reactor is introduced in this paper. It is preliminarily judged in accordance with its structural characteristics and on-site inspection that the insulation breakdown is between the 7 th and 8 th package. It is found throughout disassembly and inspetion analysis that such contamination as bird excrement and plume is obvious on the surface of the package. creepage traces along bird excrement and traces of penetrating over fire and smoke in the 7 th and 8 th package are existed. And each layer of conductor in the package has different degree of ablation and the toughness of the insulation film of theconductor around the ablation point is good. It is inferred that the fouling on the surface of package causes wet discharge
which damages the insulation of inter-strand and the inter-layer in package with gradual accumulation and deterioration
eventually resulting in short circuit of the reactor.Accordingly
such preventive measures for operation and inspection as check of anti-corrosion coating of reactor
add of cleaning items of ventilation duct for routine maintenance
reform of reactor grille and enhancement of anti-bird performance are proposed so to ensure safe operation of the equipment.