XU SIEN, DU YAN, YANG WENLIANG, et al. Study on Long-term Live test of 1 000 kV Dead Tank Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2021, 42(5): 87-93.
XU SIEN, DU YAN, YANG WENLIANG, et al. Study on Long-term Live test of 1 000 kV Dead Tank Capacitor Voltage Transformer. [J]. Power capacitor & reactive power compensation, 2021, 42(5): 87-93. DOI: 10.14044/j.1674-1757.pcrpc.2021.05.015.
Dead tank capacitor voltage transformer(hereinafter referred to as dead tank CVT)is a kind of new type voltage transformer insulated by SF
6
gas for UHV GIS projects
which
compared with the traditional column CVT
has the advantage that the capacitance is free from the influence of stray capacitance. The error of the dead tank CVT is susceptible to such factors as temperature and frequency due to limitation of the characteristics of the capacitive device itself. For better understanding of the long-term operation condition and the error of the 1 000 kV dead tank CVT in operation
the error influencing factor is analyzed in this paper and the live
assessment system
including temperature monitoring system
fault recording system and error calibration system
is set up. The 0.2-level capacitor voltage transformer and the dead tank capacitor voltage transformer are used for error comparison so to achieve the comparison calibration and longterm live test at variation of different temperature. The study shows that the 1 000 kV dead tank CVT has good insulation performance
reasonable temperature error and can meet the needs of projects. The study results in this paper lay a foundation for the engineering application of the 1 000 kV dead tank CVT.