XU PENG, GAN QIANG, TAN TINGYUE. Fault Analysis of 35 kV Oil Immersed Shunt Reactor. [J]. Power capacitor & reactive power compensation, 2021, 42(6): 76-80.
XU PENG, GAN QIANG, TAN TINGYUE. Fault Analysis of 35 kV Oil Immersed Shunt Reactor. [J]. Power capacitor & reactive power compensation, 2021, 42(6): 76-80. DOI: 10.14044/j.1674-1757.pcrpc.2021.06.011.
一起35 kV油浸式并联电抗器故障分析
摘要
运行中并联电抗器故障将会影响系统的电能质量
对电网的安全稳定运行构成威胁
分析其故障成因对维护电网安全具有重要意义。论文针对某油浸式并联电抗器运行中多次色谱异常问题展开分析
通过三比值法得出3次可能存在的缺陷分别为过热兼放电、低温过热、电弧放电
结合最后1次的返厂拆解
得出导致电抗器色谱异常的原因为铁心片间短路引起涡流损耗增加
产生局部过热烧毁绝缘垫板
最终导致绝缘短路。为提升设备可靠性
分别从设计、投入、运行、检测、检修提出合理的防治措施
为同类型设备的隐患治理、运行维护提供借鉴。
Abstract
The fault of shunt reactor in operation will affect power quality of the system
pose a threat to the safe and stable operation of power grid
therefore
it’s of great significance to analyze the causes of its faults and maintain safety of power grid. The analysis for multiple times of abnormal chromatography problem of certainoilimmersedshuntreactorinoperationisdevelopedinthispaper.Threepossiblyexisteddefects
which is obtained by the three ratio method
are overheat and discharge
low temperature and overheat and arc discharge.Itisconcluded