WANG HUAXI, GE SHAOJIE, DONG WANGUANG, et al. Fault Analysis of 35 kV Dry-type Air Core Reactor. [J]. Power capacitor & reactive power compensation, 2014, 35(5): 92-95.
WANG HUAXI, GE SHAOJIE, DONG WANGUANG, et al. Fault Analysis of 35 kV Dry-type Air Core Reactor. [J]. Power capacitor & reactive power compensation, 2014, 35(5): 92-95. DOI: 10.14044/j.cnki.dldrq.2014.05.018.
一起35 kV干式空心电抗器故障分析
摘要
结合干式空心电抗器的绝缘材质、运行环境及运行方式的瞬变
对一起35 kV干式空心电抗器故障原因进行分析
发现导致故障发生的主要原因是电抗器的绝缘材质耐热等级低和电容器组的频繁投切导致绕组局部匝间绝缘击穿
造成电流急剧增大
大电流产生高温诱使绕组绝缘相对薄弱处发生匝间短路。并针对性提出故障防范措施
为电抗器的安全运行提供保障。
Abstract
In this paper
the fault of 35 kV dry type air core reactor is analyzed based on the combination of insulation material
service environment and transients of operation mode. It is found that the main reason of the fault is the low thermal withstand level of insulation material and the frequent switching of capacitor bank
leading to insulation breakdown between partial turns of winding and significant increase of current. The high temperature due to high current induces inter-turn short circuit of winding at relative weak insulation place. The precautionary measures are proposed which provide assurance for safe operation of reactor.
关键词
干式空心电抗器匝间短路故障分析防范措施
Keywords
dry-type air core reactorinter-turn short circuitfault analysispreventive measures